Possible Problems
1 - Pump does not stop
a) - Water losses over 0.8 LPM. In some Point:
Check the installation, taps, W.C., etc.
b) - Insufficient pressure:
Check the pump pressure to be enough for each Pressure Control Switch model. (FSC15 min 2 bar; FSC22 min 3 bar; RSC15 0.5bar more than the adjusted pressure).
c) - Air inlet in the suction line of the pump:
In this event the pressure gauge will show a substantial low pressure or constant oscillation. Check leaking of joints in the suction line.
d) - Failure in the electronic circuit or blocked internal valve:
Switch off power supply. Check by withdrawing the electronic circuit from the housing. Complete with the electrical connections. If the pump continues to run then the electronic circuit requires replacement.
e) - Incorrect electrical connection:
Verify the connections are according to Fig 3 of the installation guide.
2 - Pump does not start
a) - No water supply and the security system has acted:
Check the water supply. Restart the pump through the red reset switch.
b) - Faulty pump:
Contact the technical dept of the pump company.
c) - No electrical supply:
Verify the electrical supply.
d) - Failure in the electronic circuit:
Switch off the power supply and wait a few seconds. Turn the pump on again. If the pump does not start immediately, replace the circuit.
3 - Pump starts and stops constantly
a) - Small loss in some installation points:
Verify possible water loss from taps, toilets, etc and proceed in resolving the problem |